AscInputModes

Input mode no / nc / serialResistorNo / serialResistorNc / parallelResistorNo / parallelResistorNc / dualResistorNo / dualResistorNc (optional) - Default nc (normally closed) mode.

Overview of AscInputModes goes here.

Name Value Description
Normal 0 nc - normally closed digital - open cable will activate the condition
Supervised 1 no - normally open digital - closed cable will activate the condition
SerialResistorNo 2 serialResistorNo - normally open serial resistor EOL - closed (i.e. resistor value) will activate the condition
SerialResistorNc 3 serialResistorNc - normally closed serial resistor EOL - open cable will activate the condition
ParallelResistorNo 4 parallelResistorNo - normally open parallel resistor EOL - closed cable will activate the condition
ParallelResistorNc 5 parallelResistorNc - normally closed parallel resistor EOL - open (i.e. resistor value) will activate the condition
DualResistorNo 6 dualResistorNo - normally open dual resistor EOL - closed (i.e. low resistor value) will activate the condition
DualResistorNc 7 dualResistorNc - normally closed dual resistor EOL - open (i.e. high resistor value) will activate the condition